Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 06/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUND RODS AND CONNECTION APPROVED 2) MAIN BONDING JUMPER REQUIRED BETWEEN NEUTRAL AND GROUND BAR 3) NEED BUSHING IN WHERE FEEDER WIRE EXIST EMT CONNECTORS 4) ONE SLB CONDUIT COVER NOT ACCESSIBLE |