Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 4/30/03 AT 9:15AM OK TO CLEAR. | |
| 04/09/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*CANCEL BY CONTRACTOR. | |
| 03/27/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) GAS & WATER BONDS TO BE ACCESSABLE 2.) AN APPROVED FITTINGS IS NEEDED AT LB-CHASE NIPPLE IS NOT APPROVED. 3.) USE CORRECT SIZED LUG FOR CONDUCTOR 4.) A SPLIT BOLT IS LISTED FOR ONLY 2 CONDUCTORS A RUN & A TAP. 5.) PLEASE OPEN TRENCH FOR INSPECTION OF NEW PVC CONDUIT. 6.) PROTECT AND SUPPORT PVC CONDUIT ABOVE GRADE. 7.) PROPERLY INSTALL ELECTRIC IN LAUNDRY ROOM. |