| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*0000*sent to tep on 4/1/03 at 9:15am ok to clear ok cable drop. | |
| 03/27/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* CHASE NIPPLE NOT ALLOWED AS A TERMINATION FITTING FOR 3/4" LB AT BOTTOM OF PANEL, USE CLOSE NIPPLE WITH LOCKNUTS. 2.) RELEASE OF POWER WILL NOT BE GRANTED TILL PROPER PERMIT & INSPECTIONS VERIFIED FOR NEW AC UNIT. |