Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 4/09/03 AT 2:15AM 1.) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 2.) PLEASE CALL IN OTHER PERMIT. OK TO RECONNECT. |
|
| 03/21/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) WE HAVE GROUNDED RECEPTACLE ON N UNGROUNDED SYSTEM. 2.) WE HAVE EXPOSED AND BARE CONDUCTORS. 3.) SUB PANEL IN CLOSET NOT WIRED SAFELY. 4.) MAINTAIN WORKING CLEARENCES INFRONT OF SERVICES. 5.) PROTECT CONDUCTORS ENTERING SERVICE DISCONNECT. 6.) FUSE AMPACITY TO MATCH CONDUCTORS SIZING. 7.) A LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK. |