Permit: T03EL00510

Parcel: 122080140


Addresses:

4144 E GRANT RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 4/09/03 AT 2:15AM
1.) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL
2.) PLEASE CALL IN OTHER PERMIT.
OK TO RECONNECT.
03/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) WE HAVE GROUNDED RECEPTACLE ON N UNGROUNDED SYSTEM.
2.) WE HAVE EXPOSED AND BARE CONDUCTORS.
3.) SUB PANEL IN CLOSET NOT WIRED SAFELY.
4.) MAINTAIN WORKING CLEARENCES INFRONT OF SERVICES.
5.) PROTECT CONDUCTORS ENTERING SERVICE DISCONNECT.
6.) FUSE AMPACITY TO MATCH CONDUCTORS SIZING.
7.) A LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK.