Permit: T03EL00486

Parcel: 120072090

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/17/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TO CLEAR, OK CABLE DROP 2) MAKE SURE ELECTRICIAN IS ON SITE AT TIME OF OUTAGE TO DISCONNECT FEEDER 3) SENT TO TEP 6/18/03 915AM
05/22/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NOT LEFT BY CONTR. JOHN STATING THAT 2ND METER IS FOR OWNER TO MONITOR POWER CONSUMPTION BY SECOND UNIT. NOT TO BE CONNECTED TO UTILITIE POWER. SECOND METER IS TIED IN TO EXIST SERVICE CIRCUIT BREAKER AT MAIN HOUSE.
05/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.)INSTALL ADDRESS/UNIT # ON SERVICE ENCLOSURE.
2.) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT SECOND STRUCTURE PER ART 250 NEC.
3.) IS THIS SECONDARY METERING,? OR DO YOU INTEND TO USE UTILITE POWER?
4.) VERIFY C-11 LICENSED CONTR.
5.) CANNOT HAVE UTILITIES POWER AND COSTUMER POWER IN SAME ENCLOSURE (BREAKER PANEL) 230 NEC.
04/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*INSTALL NEW METER.
REMOVE COVER PLATES TO ALL DEVICES.