Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/20/03 AT 9:15AM | |
| 03/18/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210* THE FOLLOWING ARE REQUIRED. 1.) PERMANENT ADDRESS ON ELECTRIC PANEL. DO NOT USE "MAGIC MARKER", PEN OR PENCIL. 2.) MARK CIRCUIT INDEX TO IDENTIFY CIRCUITS. YOU MAY USE "MAGIC MARKER SHARPIE INSIDE THE PANEL. 3.) EXPOSE THE GROUND RODS FOR INSPECTIONS DOWN TO THE CLAMP LOCATION. 4.) THE GAS LINE MUST BE BONDED TO THE WATER LINE. THIS CAN BE DONE AT THE WATER HEATER. 5.) A SMOKE DETECTOR WILL BE REQUIRED IN THE HALLWAY. CORRECT & RECALL THANKS BEFORE BEDROOMS. |