Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/12/03 @ 9:15AM OK TO CLEAR UPGRADE. | |
| 05/02/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*FINISH PREVIOUS ITEMS AS DISCUSSED. | |
| 04/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. | |
| 03/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) USE APPROVED FITTINGS AT LB CHASE NIPPLES NOT APPROVED. 2.) A BONDING DEVICE IS NEEDED ON SERVICE NIPPLE TO METER BOTH SIDES. 250-94. 3.) IDENTIFY BONDING JUMPING AS PER CODE 250-119 4.) SEALING DEVICES ARE NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. |
|
| 03/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. | |
| 03/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. |