Permit: T03EL00447

Parcel: 130120350


Addresses:

3746 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/25/2003 ELECTRIC - FINAL Approved 1.) FLOURESCENT LIGHTING REAR ROOM EXPOSED BELOW 8'
2.) OUTDOOR WIRING WEST GARAGE TO BE REMOVED. 2ND INSP OK TO CLEAR RECONNECT.
03/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) FLORESCENT LIGHTS REAR ROOMS WIRING TO E PROTECTED PHYSICALLY.
2.) 20 AMP CIR FEEDING OUTLET TO SIDE OF PANEL, THE WIRING EXITING RECEPTACLE HAS TO BE PHYSICALLY PROTECTED ALSO THIS WIRING IS JUST UNDER SHEET ROCK WHERE ITS NAILED.
3.) CEILING FAN IN BACK ROOM WIRIED INCORRECTLY ALSO REMOVE ZIP CORD FEEDING IT,
4.) GARAGE WIRING TO LIGHT AND GARGARE DOOR MOTORS CANNOT OF THUR CIELING TILE.
5.) FAN IN WEST GARAGE OPEN WIRED OPEN SPLICE ALSO ALL WIRING BY DOOR & WINDOW.
OBTAIN THE SERVICES OF A LICENSED ELECTRICAN TO REMOVE ALL VIOLATIONS AND PROBLEMS AND CHECK ALL ELECTRICAL FOR SAFETY.
THEN RECALL FOR CITY INSPECTION TO CHECK.