Permit: T03EL00412

Parcel: 115051420


Addresses:

10 W RILLITO ST #05

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/15/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0165*CORRECTIONS NEEDED,
1.) ATTACH PERMANENT ADDRESS NUMBER TO PANEL. NO MAGIC MARKER,' OR PENCIL.
2.) INSTALL SMOKE DETECTOR IN BEDROOM.
03/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*NEC ART 380-8.
REQUIRES THAT CIRCUIT BREAKERS NOT BE LOCATED HIGHER THAN 6' FT 7" INCHES ABOVE NATURAL GROUND LEVEL. THE PANEL MUST BE LOWERED.