Permit: T03EL00411

Parcel: 107081430


Addresses:

850 W JACINTO ST

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/03/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
07/30/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CLEARANCE SUBJECT TO PERMIT FOR INTERIOR WIRING

NO PERMIT FOR INTERIOR WIRING,
ALL NEW CIRCUITS PULLED IN
02/23/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL ROOF FLASHING
2. PROVIDE ADDITIONAL MAST STRAP
3. USE OXIDE INHIBITOR ON ALUMINUM TERMINATIONS
4. TERMINATE EQUIPMENT GROUNDS PER INSTRUCTION LABEL IN PANEL.
5. MULTI-WIRE BRANCH CKT TO BE ON SEPARATE PHASES.
6. INTERIOR WIRING/WORK TO BE PERMITTED/INSPECTED.