Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*DENIED NOTE OK W/MIN HOUSE INSPECT. 1.) KITCHEN COUNTER RECEPTACLES IMPROPER WIRING METHODS TERMINATIONS, BOX OVERFILL, SINGLE CONDUCTORS. MUST CORRECT AND HAVE LICENSED C-11 CONTRACTOR CHECK OUT REST OF HOUSE. 2.) NEED A SERVICE UPGRADE PERMIT AND CALL FOR THE SERVICE INSPECTION. 3.) WILL NEED ACCESS TO GUEST HOUSE. |
|
| 03/10/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*NOTES KNOCKED TWICE NO ANSWER, DOOR LOCKED, GATE LOCKED NO MSG. A REINSPECTION FEE IS ASSESSED. PLEASE PAY RE-FEE 201 N STONE PRIOR TO FUTURE INSP. |
|
| 03/07/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*NOTES 1.) NO ANSWER AT DOOR, DWELLING LOCKED, MUST BE ACCESSABLE TO INSPECTOR, PLEASE RE CALL INSPECTION WHEN ACCESS GRANTED. 2.) HOUSE POSTED AS UNSAFE BLD. BY MIN HOUSING DUE TO NO POWER ON PREMISES, RAY CAMACHO. |