Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR | |
| 09/13/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/WELL METER 1)WE HAVE EXPOSED CONDUCTORS & CABLE TO EQUIPMENT 2)SUPPORT PVC CONDUIT TO PANEL/PUMP DISCONNECT-PLEASE VERIFY SCHED? 80? 3)REINSTALL ARC SHEILD 4)LABEL BRAKERS & EQUIPMENT 5)FILL UNUSED OPENING IN PANEL 6) CLEAN SURFACE UNDER GROUND BAR MAIN SERVICE: 1)REJECTION PINS ACD NEEDED WITH FUSES 2)MAIN BONDING JUMPER NOT TO USE CAN AS PATH OF GROUND 3)FILL UNUSED OPENING IN GUTTER 4)CLEAN SURFACE UNDER GROUND BAR 5)PLANS NOT REFLECTION OF WORK INSTALLED-PLEASE REVISE |
|
| 05/18/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000**SENT TO TEP ON 5/19/03 AT 9:15AM PLEASE VERIFY PERMIT FOR WORK BEING DONE AT MAIN BUILDING. OK TO CLEAR UPGRADE. |