Permit: T03EL00381

Parcel: 111060820

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO RECONNECT.sent to tep on 3/14/03 at 9:15am
03/06/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) WE HAVE GROUNDED RECEPTICALS ON AN UNGROUND CIRCUIT
2.) PLEASE HAVE AN ELECTRICAN CLEAN UP NEUTRAL TERMANALS AT SUBPANEL BOX WE ALSO HAVE MULTIPOLE TERMANNATIONS UNDER SCREWS.
3.) RECEPTICAL IN CLOSET NOT INSTALLED AS CODES ALLOW.
4.) WIRING IN GARAGE AREA BE LOW 8' TO HAVE PHYSICAL PROTECTION.
PLEASE HAVE LICENSED ELECTRICAL CONTRACTOR PERFORM THE WORK AND RECALL FOR INSPECTION.