Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*sent to tep on 4/1/03 at 9:15 make sure that ko seals are rain proof. 2.) need jumper to neutral at c.t. can from grnd. card to neutral ok for temp power. |
|
| 03/26/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*NEED NEUTRAL TO EACH SERVICE DISCONNECT. NEED TO BOND EACH SERVICE DISCONNECT NEED GROUNDING BUSHINGS & BOND JUMPER THROUGHOUT IDENTIFY ALL WITH PROPER METAL TAG. CONDENSATE LINER DO NOT AFFORD PROPER CLEANANCE IN FRONT OF DISCONNECT. |