Permit: T03EL00378

Parcel: 13409018C


Addresses:

8600 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/01/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*sent to tep on 4/1/03 at 9:15 make sure that ko seals are rain proof.
2.) need jumper to neutral at c.t. can from grnd. card to neutral ok for temp power.
03/26/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*NEED NEUTRAL TO EACH SERVICE DISCONNECT.
NEED TO BOND EACH SERVICE DISCONNECT NEED GROUNDING BUSHINGS & BOND JUMPER THROUGHOUT
IDENTIFY ALL WITH PROPER METAL TAG.
CONDENSATE LINER DO NOT AFFORD PROPER CLEANANCE IN FRONT OF DISCONNECT.