Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/13/03 AT 9:15AM OK TO CLEAR. | |
| 03/10/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PLEASE VERIFY WATER BOND TO INTERIOR PIPING. 2.) ALL ENTRANCES ABOVE CURRENT CARRING PARTS TO BE SEALED. 3.) USE CORRECT COLOR CODING FOR GROUNDING AND NEUTRAL CONDUCTORS AND HOT CONDUCTORS BOTH JUNCTION BOXES. 4.) LB COVER TO BE ACCESSABLE. 5.) ALL RISER HARDWARE TO BE 1/4" MININUM. |
|
| 03/05/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. |