Permit: T03EL00350

Parcel: 112060500


Addresses:

2649 N PLUMER AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/04/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 3/5/03 AT 9:15AM OK TO CLEAR.
02/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SEALING DEVICES ARE NEEDED FOR ENTRANCES ABOVE CURRENT CARRYING PARTS.
2.) TIGHTEN LOOSE FITTINGS.
3.) RISER HARDWARE AND PANEL SUPPORTS TO BE 1/4" MINIMUM.
4.) PLEASE VERIFY JUNCTION BOX ENCLOSURE BONDING.