Permit: T03EL00331

Parcel: 122081050

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 4/8/03 AT 9:15AM OK TO CLEAR.
04/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) PLEASE TERMANATE STRADED CONDUCTORS WITH ALL STRANDS A BREAKERS.
2.) WE STILL HAVE A ADDRESS PROBLEM #2 PREVIOUS INSPECTION.
03/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) PLEASE VERIFY LICENSE CONTRACOR #.
2.) PERMIT TO REFLECT CORRECT ADDRESSING # 2 IS OLD SERVICE.#1 IS NEW.
3.) PLEASE LABEL ALL BREAKERS.
4.) OLD PANEL NOT LISTED AS A JUNCTION BOX. A LISTED BOX IS NEEDED.
5.) GAS & WATER FOR MAIN HOUSE ALSO TO BE BONDED.
6.) DERATE FOR CONDUCTORS IN CONDUIT AS PER CODE 310-15.