Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 4/8/03 AT 9:15AM OK TO CLEAR. | |
| 04/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) PLEASE TERMANATE STRADED CONDUCTORS WITH ALL STRANDS A BREAKERS. 2.) WE STILL HAVE A ADDRESS PROBLEM #2 PREVIOUS INSPECTION. |
|
| 03/27/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) PLEASE VERIFY LICENSE CONTRACOR #. 2.) PERMIT TO REFLECT CORRECT ADDRESSING # 2 IS OLD SERVICE.#1 IS NEW. 3.) PLEASE LABEL ALL BREAKERS. 4.) OLD PANEL NOT LISTED AS A JUNCTION BOX. A LISTED BOX IS NEEDED. 5.) GAS & WATER FOR MAIN HOUSE ALSO TO BE BONDED. 6.) DERATE FOR CONDUCTORS IN CONDUIT AS PER CODE 310-15. |