Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03EL00319
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/25/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0215* THE EMT STUBS (3-4)" MUST BE BONDED TO THE SERVICE GROUND. THE LOCKNUTS ARE NOT SUFFICIENT. PLEASE SEE NEC 104 W/FINE PRINT NOTES. 2.) UNBUNDLE THE CONDUCTORS IN THE GUTTER. BUNDLING CAUSES HEAT BUILD UP AND POSSIBLY MAGNETIC INDUCTION. |