Permit: T03EL00319

Parcel: 11706168C


Addresses:

318 E CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/26/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/25/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0215*
THE EMT STUBS (3-4)" MUST BE BONDED TO THE SERVICE GROUND. THE LOCKNUTS ARE NOT SUFFICIENT. PLEASE SEE NEC 104 W/FINE PRINT NOTES.
2.) UNBUNDLE THE CONDUCTORS IN THE GUTTER. BUNDLING CAUSES HEAT BUILD UP AND POSSIBLY MAGNETIC INDUCTION.