Permit: T03EL00299

Parcel: 11008165B


Addresses:

4520 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT 2/4/04 TO TEP
01/29/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) MEET TOM PALM FROM PALM ELECTRIC TO DISCUSS JOB
11/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PLEASE COMPLETE ITEMS #9 AND 10 BEFORE ANY FUTHER INSPECTIONS
02/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) A PERMANENT METAL ADDRESS LABEL IN REQUIRED.
2.) PLEASE VERIFY GROUNDING AND BONDING.
3.) LB COVER IS TO BE ACCESSABLE.
4.) LABEL BREAKERS.
5.) TIGHTEN FITTING AT LB.
6.) CONDUCTORS NOT ALLOWED TO BE TRIMED
7.) USE AN APPROVED LUG FOR GROUNDED CONDUCTOR.
8.) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES LABEL.
9.) A LICENSE ELECTRICAL CONTRACTOR IS NEEDED. THIS CONTRACTOR HAS ONLY A RESIDENTIAL "B" LICENSE.
10.) PLEASE VERIFY ANY OTHER PERMITS TO HAVE RELEASED POWER TO TEP.