Permit: T03EL00298

Parcel: 133130090


Addresses:

7700 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/26/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 2/27/03 AT 9:15AM OK TO CLEAR.
02/25/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) BOND GAS GROUNDING CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR ACORN CLAMP LISTED FOR ONLY 1 CONDUCTOR.
2.) LABEL BREAKERS.
3.) ANTI OXIDE COMPOUND IS NEEDED FOR GROUNDING CONDUCTOR.
4.) MAINTAIN WORKING CLEARENCE IN FRONT OF SERVICE 110-26. OWNER STATES SHED WILL MOVE WHEN NEW SHED IS BUILT. A JACUZZI WILL OCCUPY SLAB. A PERMIT WILL BE REQUIRED FOR THAT INSTALLATION.