Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 2/27/03 AT 9:15AM OK TO CLEAR. | |
| 02/25/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) BOND GAS GROUNDING CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR ACORN CLAMP LISTED FOR ONLY 1 CONDUCTOR. 2.) LABEL BREAKERS. 3.) ANTI OXIDE COMPOUND IS NEEDED FOR GROUNDING CONDUCTOR. 4.) MAINTAIN WORKING CLEARENCE IN FRONT OF SERVICE 110-26. OWNER STATES SHED WILL MOVE WHEN NEW SHED IS BUILT. A JACUZZI WILL OCCUPY SLAB. A PERMIT WILL BE REQUIRED FOR THAT INSTALLATION. |