Permit: T03EL00288

Parcel: 122160470


Addresses:

2260 N CHRYSLER DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/26/2003 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
02/21/2003 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*INSTALL CORRECT WATER BOND CLAMP ON WATER LINE NEXT TO SERVICE.
2.) REMOVE LIGHT IN SOUTH WEST BEDROOM AND INSTALL DEVICE PLATE CORRECTLY (LIGHT INSTALLED INCORRECTLY.).
3.) ALL BEDROOMS REQUIRE SMOKE DETECTORS ROAD INSTALLATION INSTRUCTIONS PRIOR TO INSTALL BATTERY TYPE OK
4.) PANEL IN CLOSET OK.
5.) WIRING IN STORAGE ROOM TO BE CORRECTED OR REMOVED. ALL ROMEX TO BE PHYSICALLY PROTECTED UP TO 8'.
6.) PROVIDE A WEATHER PROOF BOX AND COVER FOR COOLER RECEPTACLE ON ROOF FOR COOLER.
7.) THEIR ALL SOME GROUNDED AND UNGROUNDED OUTLETS IN HOUSE HAVE ELECTIRCAN CHECK ALL RECEPTACLES TO VERIFY GROUND MEANS OR CHANGE ALL TO UNGROUND TYPE.