Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*SENT TO TEP ON 2/26/03 AT 9:15AM APPROVED AND ADDITIONAL CIRCUITS. | |
| 02/25/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) DRIVE GROUND RODS FLUSH OR BELOW GRADE 2.) PERMANENTLY ADDRESS METER USE METAL TAGS AND INSTALL WITH REVIETS OR SCREWS. 3.) MUST VERIFY THAT ALL CIRCUITS ARE IN FACT RATED AT 20 AMPS. 4.) 4 ADDITIONAL CIRCUITS HAVE BEEN INSTALLED IN HOUSE. A PERMIT, PLAN AND & DISCRIPTION OF WORK MUST BE MADE UP AND SUBMITTED TO DSD. 5.) HOUSE HAS GROUNDING STYLE RECEPTACLES IN UNGROUNDED SYSTEM, MUST CHANGE. ALSO REVERSED POLARITY HAS BEEN NOTED. 6.) CALL 791-5550 FOR RESIDENTIAL PLANS EXAMINER FOR MORE INFORMATION ON WHAT IN REQUIRED ON PLAN. WALK MAY HAVE TO BE OPENED FOR INSPECTION. |