Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/4/03 AT 9:15AM OK TO CLEAR UNIT 2102 ONLY OTHERS CLEARED. | |
| 03/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) OK TO SEND CLEARANCE FOR UNITS 1104-1107 AND 2104. 2.) UNIT 2102 HAS NOT BEEN FITTED WITH SMOKE DETECTORS. |
|
| 02/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0165* EACH BEDROOM MUST HAVE A SMOKE DETECTOR THESE MAY BE BATTERY OPERATED. MOUNTING LOCATION SHOULD BE. 1.) 3 FT. DISTANCE TO SUPPLY AIR GRILL/OPENING. 2.) ON WALL NOT CLOSER THAN 6" TO CIELING OR LOWER THAN 12" FROM CIELING. 3.) IF CIELING MOUNTED NOT CLOSER THAN 16" TO WALL OR CORNER. INSTALL AND RECALL INSPECTION. |