Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 2/19/03 AT 9:15AM OK TO CLEAR RE-CONN. |
| 02/18/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: INSTALL PERMANENT ADDRESS LABEL ON SERVICE. MUST BE SCREWED OR RIVITED TO ENCLOSURE 2) ID CIRCUIT BREAKERS. LABEL UNIT # 3) WIRE SPLICE AT WEATHER HEADS NOT INSULATED 4) INSTALL SMOKE DETECTOR IN BEDROOM 5) TRI-PLEX BETWEEN UNITS MUST BE 12' ABOVE GROUND |