Permit: T03EL00258

Parcel: 111080340


Addresses:

3514 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/20/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 2/21/03 AT 9:15AM APPROVED OK TO CLEAR UPGRADE.
02/14/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PLEASE USE AN APPROVED CONNECTOR AT LL-A CHASE NIPPLE IS NOT APPROVED.
2.) PLEASE SMOOTH OUT SHARP EDGES ON DEAD FRONT COVER.
3.)ALL GAS SERVICES TO BE BONDED TO INTERIOR SIDE OF PIPING.
4. RISER HARD WARE TO BE 1/4" MININUM BOTH SERVICES
5.) BONDING DEVICES ARE NEEDED ON ALL FITTINGS AND NIPPLES AT SERVICE PER 250-94 AND TIGHTEN LOCKNUTS.
6.) GROUDING ELECTRODE CONDUCTOR TO BE BONDED TO GROUNDED TERMANAL AND SIZED PER 250-66.
7.) BOND GUTTER ENCLOUSER.
8.) WHERE IS GROUNDED CONDUCTOR FOR SUB PANEL?
9.) GROUNDING EQUIPMENT CONDUCTOR TO HAVE MARKINGS CONDUCTOR.