Permit: T03EL00250

Parcel: 118120620


Addresses:

227 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
07/23/2003 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection 0000*
03/12/2003 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection 0245*
1.) DRIVE GROUND ROD ALL THE WAY IN TO GROUND.
2.) BOND WATER, GAS TO GROUNDING ELECTRODE SYSTEM AT SERVICE, PER ART 250 NEC.
3.) OVER HEAD DROP FROM NEW SERVICE LOCATION TO HOUSE MUST HAVE 8' CLEARANCE ABOVE SHED AND RAMADA ROOF, PER ART 230 NEC.
4.) DEAD FRONT MISSING ON HOUSE PANEL.