Permit: T03EL00240

Parcel: 136282800


Addresses:

7701 E PERSIMMON DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/18/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*ELECTRIC UPGRADE DENIED SEE WRITE UP OF 3/5/03 ON THE HOUSE ADDITION THE PERMIT EXPIRED AND NO FINAL INSPECTION IS ON HAND.
THE OLD ACTIVITY NUMBER T97CM02045 MUST BE RENEWED AND INSPECTIONS BY THE GENERAL INSPECTOR MUST BE CALLED FOR YOUR FINAL.
03/17/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*WILL BE REQUESTING POWER TURN OFF.
03/05/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*HOUSE APPEARS TO HAVE BEEN ADDED TO NEW ADDITION.
OLD SERVICE AREA IS NOW A JUNCTION BOX WITH REFED BRANCH CIRCUITS, THIS REWIRING AND THE WIRING METHOD PER THE 99 N.E.C. ART 300 IS IMPROPER.
NEED TO SEE A COMPLETE SET OF APPROVED PLANS WITH THE ELECTRICAL, PLUMBING, MECHANICAL AND STRUCTURAL DETAILS.
IF THERE IS NO PROOF OF APPROVALS WITHIN 5 WORK DAYS A POWER DISCONNECTION WILL BE REQUESTED FROM THE POWER COMPANY.
APPROVED CITY PLANS (ACCURATE AS BUILT) AND ALL OF THE INSPECTIONS APPROVALS.
02/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 2/12/03 AT 9:15AMTHIS IS A SERVICE RELOCATION INSPECTOR NEEDS TO SEE ROUTED BRANCH CIRCUITS TO NEW SERVICE LOCATION. HOUSE LOCKED, MEET INSPECTOR ON SITE IF POSSIBLE NEXT INSPECTION.
2.) ROMEX RUN THRU STORAGE ROONM CANNOT BE EXPOSED, MUST BE COVERED.