Permit: T03EL00235

Parcel: 127031060


Addresses:

5743 E 2ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL00235

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/30/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR
06/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PLEASE SECURE RISER SUPPORT-1/4" MINIMUM HARDWARE 2) IDENTIFY GROUNDING CONDUCTOR AT TERMINAL 3) SUPPORT CONDUIT AS PER CODE 4) SECURE GROUNDING ELECTRODE CONDUCTOR WITH APPROVED MEANS-TY WRAPS ARE NOT UV RATED 5) BOND JUNCTION BOX ENCLOSURE WITH SPLICES
02/20/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) PERMANENT ADDRESS ON SERVICE REQUIRED
2.) WHEN A SERVICE IS INCREASED OR UPGRADED IT MUST COMPLY WITH 99 NEC 110-26 COMPLETE CLEARANCE DOWN TO GROUND THE WIDTH OF SERVICE OR 30" IS REQUIRED GAS METER CANNOT BE INFRONT OF NEW PANEL.
3. NEED AC PERMIT.