Permit: T03EL00225

Parcel: 105130700


Addresses:

308 E LIMBERLOST DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/21/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*Sent to TEP ON 2/24/03 AT 9:15AM.
02/19/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210* CORRECTIONS REQUIRED 1) THE MAIN CIRCUIT BREAKER CANNOT BE LOCATED HIGHER THAN 6' 7'' FROM GRADE. ART. 380-8 NEC 2) THE COLD WATER AND GAS PIPES MUST BE BONDED/GROUNDED TO THE NEW GRONS SYSTEM OR PANEL 3) THE ADDRESS ON THE PANEL MUST BE OF METALLIC NUMBERS-RESISTANT TO THE AMBIENT.MAGIC MARKER, PEN OR PENCIL ARE NOT ALLOWED.