Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/21/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*Sent to TEP ON 2/24/03 AT 9:15AM. |
| 02/19/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210* CORRECTIONS REQUIRED 1) THE MAIN CIRCUIT BREAKER CANNOT BE LOCATED HIGHER THAN 6' 7'' FROM GRADE. ART. 380-8 NEC 2) THE COLD WATER AND GAS PIPES MUST BE BONDED/GROUNDED TO THE NEW GRONS SYSTEM OR PANEL 3) THE ADDRESS ON THE PANEL MUST BE OF METALLIC NUMBERS-RESISTANT TO THE AMBIENT.MAGIC MARKER, PEN OR PENCIL ARE NOT ALLOWED. |