Permit: T03EL00225

Parcel: 105130700


Addresses:

308 E LIMBERLOST DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/21/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
02/19/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210* CORRECTIONS REQUIRED 1) THE MAIN CIRCUIT BREAKER CANNOT BE LOCATED HIGHER THAT 6' 7'' FROM GRADE. ART. 380-8 NEC 2) THE COLD WATER AND GAS PIPES MUST BE BONDED /GROUNDED TO THE NEW GROUND SYSTEM OR PANEL. 3) THE ADDRESS ON THE PANEL MUST BE OF METALLIC NUMBERS- RESISTANT TO THE AMBIENT MAGIC MARKER, PEN , OR PENCIL ARE NOT ALLOWED