Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 2/26/03 AT 9:15AM OK TO CLEAR. | |
| 02/05/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) CAN NOT ENTER THIS PANEL AT TOP END WALL AS PER MANUFACTURES LABEL. 2.) PERMANET METHOD FOR LABELING BREAKERS IS NEEDED NOT INK PEN. 3.) PLEASE INDENTIFY NEUTRAL CLOSER TO WEATHER HEAD. 4.) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMANAL LUG. 5.) 1/4" MININIUM HARDWARE IS NEEDED FOR RISER SUPPORTS AND SERVICE EQUIPMENT. 6.) PROTECT CABLE ENTERING CONDUIT. OK TO DRIVE GROUND RODS FLUSH TO GRADE. |