Permit: T03EL00208

Parcel: 123070730


Addresses:

2001 E MABEL ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/25/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 2/26/03 AT 9:15AM OK TO CLEAR.
02/05/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) CAN NOT ENTER THIS PANEL AT TOP END WALL AS PER MANUFACTURES LABEL.
2.) PERMANET METHOD FOR LABELING BREAKERS IS NEEDED NOT INK PEN.
3.) PLEASE INDENTIFY NEUTRAL CLOSER TO WEATHER HEAD.
4.) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMANAL LUG.
5.) 1/4" MININIUM HARDWARE IS NEEDED FOR RISER SUPPORTS AND SERVICE EQUIPMENT.
6.) PROTECT CABLE ENTERING CONDUIT.
OK TO DRIVE GROUND RODS FLUSH TO GRADE.