Permit: T03EL00198

Parcel: 111072860

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL00198

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/23/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SEE NOTES #1,#2,#9.
04/16/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0910*NO ACCES TO BACK UNITS DUE TO DOGS.
04/09/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) BOND ALL GAS SERVICES.
2.) HIGHEST AVAILABLE BREAKER NOT TO BE OVER 6' 7" TO HANDLE
3.) WHAT IS SUB FEED FOR
#2 & #3
1.) TIGHTEN LOOSE FITTINGS
2.) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS.
3.) BONDING JUMPER TO BE SIZED PER 250-66.
4.) A CLAMP IS NEEDED FOR GROUND AT SUBPANEL.
5.) ATTACH JUNCTION BOX TO STRUCTURE.
6.) A GROUNDING EQUIPMENT CONDUCTORS ARE NEEDED.
7.) BALANCE LOAD FOR BRANCH CIRCUITS 210-11.
8.) LABEL SUBPANELS
9.) BOND BOTH WATERS.
03/19/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*HAVE LICENSED ELECTRIC CONTRACTOR CALL ME AT THE OFFICE BEFORE NEXT INSPECTION. WE HAVE NEUMERIOUS DISCREPENCIES.