Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | ||
| 02/20/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* 1.) THIS IS NOT AN UPGRADE TO 200 AMPS. A NEW 60 AMPS SUBPANEL WAS JUST ADDED TO EXISTING 100 AMP SERVICE. 2.) THE SUBPANEL HAS TO BE WEATHER PROOF INSTALLED OUTSIDE UNDER PORCH DOES NOT COUNT. 3.) NO MAIN BREAKER ON NEW SUBPANEL. 4.) # |
|
| 02/19/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1.) THIS IS NOT AN UPGRADE T0 200AMP. A NEW 60 AMP SUBPANEL WAS JUST ADDED TO EXISTING 100 AMP SERVICE. 2.) THE SUBPANEL HAS TO BE WEATHER PROOF INSTALLED OUTSIDE UNDER PORCH DOES NOT COUNT. 3.) NO MAIN BREAKER ON NEW SUBPANEL. 4.) #14 CIRCUIT SHOULD NOT BE ON 20 AMP BREAKER. 5.) GROUNDS AND NEUTRALS NOT TO BE CONNECTED TOGETHER AT SUBPANEL. 6.) 3/4" PVC RUN INCORRECTLY CANNOT RUN ROMEX IN IT, SOME SECTIONS NOT GLUED TOGETHER NOR PROPERLY SUPPORTED. 7.) NEW A PLAN AND PERMIT FOR NEW FEED TO REAR UNIT. ALL OF THESE ITEM NEEDS CORRECTION SUGGEST YOU OBTAIN THE SERVICE OF A C-11 LICENSED ELECTRICAN TO CORRECT. 8.) INSTALL ORIGINAL DEAD FRONT COVER. FOLLOW UP WILL BE IN 30 DAYS. |