Permit: T03EL00174

Parcel: 124050870


Addresses:

711 E 5TH ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL00174

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
02/05/2003 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
1.) REMOVE THE CHASE NIPPLE FROM THE LB. USE A CLOSED SHORT THREADED NIPPLE AND LOCKNUTS. IT HAS BEEN FOUND THE THE TAPED SHOULDER OF THE CHASE NIPPLE DOES NOT.
PROVIDE A "POSITION" GROUNDING CONNECTION FO RTHE CONDUIT.
2.) EXPOSE THE GROUND ROD ENDS FOR INSPECTION.
3.) ONLY ONE RUN OF GROUND WIRE IS NEEDED. YOU MAY CONNECT GROUND FROM ONE PANEL TO THE OTHER.
4.) LEAVE A SHORT SAMPLE OF THE SERVICE RISER CABLE. I NEED TO CONFIRM SIZE, AMPERAGE, AND INSULATION (MUST BE SUN LIGHT RESISTANT.)