Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 02/24/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*GROUND RODS TO BE LAYED IN TRENCH 30" DEEP 6' APART NOT ANGLED OR BENT. 2.) CANNOT DOUBLE TWO #4 BARE GROUND ON ONE LUG LUG APPROVED FOR ONE CONDUCTOR. |