Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP 2/6/03 AT9:15AM |
| 01/29/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) NEW SERVICES REQUIRE A COMPLETE NEW GROUNDING SYSTEM. THE WATER AND GAS PIPING MUST BE BONDED TO THE PANEL. NEC. ARTICLE 250-104 2) THE GROUND WIRE ON THE END GROUND ROD MUST BE IN THE "POCKET" OF THE CLAMP-NOT UNDER THE SCREW 3) THE PULL OUT SWITCH ABOVE THE PANEL MUST BE LOCATED NOT HIGHER THAN 6'-7" FROM GRADE 4) IDENTIFY THE DISCONNECT. WHAT DOES IT SERVE? 5) MAXIMUM HEIGHT ON CIRCUIT BREAKERS IS 6'-7". MOVE BREAKERS DOWN AND SEAL C/B OPENINGS ABOVE 6'-7" SEE NEC. ARTICLE 380-8, CORRECT AND RECALL. LEAVE INFORMATION NOTE AS TO WHERE GAS AND WATER BONDS ARE LOCATED |