Permit: T03EL00146

Parcel: 120082500


Addresses:

4766 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2003 ELECTRIC - FINAL Approved OK TO CLEAR OK CABLE DROP
02/10/2003 ELECTRIC - FINAL Denied 1.) BOND BUSHINGS NOT BONDED.
2.) SHEET METAL SCREWS NOT ALLOWED TO SECURE GROUND LUG TO ENCLOSURE AT DISCONNECT, USE NUT AND BOLT. 250-8 NEC.
01/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) PERMANENT ADDRESS LABEL REQUIRED ON SERVICE.
2.) BOND LOCKNUTS OR BOND BUSHINGS REQUIRED BOTH ENDS OF 2 1/2" NIPPLE BETWEEN METER BASE AND SERVICE DISCONNECT. PER ART 250NEC.
3.) NEW GROUNDING ELECTRODE SYSTEM AND EXISTING MUST BE CONNECTED TOGETHER WITH AN UNSPLICED JUMPER WHEN USING BOTH.
4.) INSTALL FUSES.