Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2003 | ELECTRIC - FINAL | Approved | OK TO CLEAR OK CABLE DROP | |
| 02/10/2003 | ELECTRIC - FINAL | Denied | 1.) BOND BUSHINGS NOT BONDED. 2.) SHEET METAL SCREWS NOT ALLOWED TO SECURE GROUND LUG TO ENCLOSURE AT DISCONNECT, USE NUT AND BOLT. 250-8 NEC. |
|
| 01/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) PERMANENT ADDRESS LABEL REQUIRED ON SERVICE. 2.) BOND LOCKNUTS OR BOND BUSHINGS REQUIRED BOTH ENDS OF 2 1/2" NIPPLE BETWEEN METER BASE AND SERVICE DISCONNECT. PER ART 250NEC. 3.) NEW GROUNDING ELECTRODE SYSTEM AND EXISTING MUST BE CONNECTED TOGETHER WITH AN UNSPLICED JUMPER WHEN USING BOTH. 4.) INSTALL FUSES. |