Permit: T03EL00122

Parcel: 11450019B


Addresses:

8610 E WOODLAND RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/15/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
03/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*Sent to TEP 3/27/03 at 9:15am A COVER THAT IS WHEATHER PROOF WHEN PLUGED IN .
2.) FINISH LABELING AT WELL PANEL OK TO CLEAR
PLEASE RECALL AFTER CROSSWORK.
03/21/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) PLEASE LABEL METERS & BREAKERS
2.) APPROVED FITTINGS ARE NEEDED FOR SEALTITE.
3.) FINISH CONNECTIONS OF WIRES
4.) DOUBLE TERMANATIONS AT CAN LUG. PLEASE PROVIDE LONG GROUND FROM LUG.
5.) FILL UNUSED OPENINGS IN PANEL FILLER BLANKS.
6.) A GAS & WATER BOND IS NEEDED.