| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 02/03/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0245*NOTES 1.) COMPLETE U.G. CONDUIT? WHAT IS 2" PVC FOR? 2.) INSTALL BREAKER BLANKS ON DEADFRONT. |
|
| 01/23/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0020*1.) THE 2 1/2 RISER PIPE IS TERMINATED IN A 3" CONCENTRIC KNOCKOUT. THE USE OF A THREADED HUB BOLTED TO THE BOTTOM OF THE PANEL IS REQUIRED. THE HUB ALSO ELIMINATES THE NEED FOR A GROUNDING BUSHING. PLEASE MAKE THIS CHANGE AND RECALL INSPECTION. THANK YOU. |