Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 1010AM |
| 10/06/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BONDING DEVICE NEEDED AT ALL POINTS AS PER 250-94 2) BONDING JUMPER SIZED PER 250.66-GUTTER, CT CAN AND ENCLOSURES 3) PLEASE PROVIDE REJECTION PINS AT DISCONNECTS |
| 10/01/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) FINISH PREVIOUS ITEMS 3) USE APPROVED SPLICING METHODS |