Permit: T03EL00058

Parcel: 111060250

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1010AM
10/06/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) BONDING DEVICE NEEDED AT ALL POINTS AS PER 250-94 2) BONDING JUMPER SIZED PER 250.66-GUTTER, CT CAN AND ENCLOSURES 3) PLEASE PROVIDE REJECTION PINS AT DISCONNECTS
10/01/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) FINISH PREVIOUS ITEMS 3) USE APPROVED SPLICING METHODS
09/24/2003 ELECTRIC - FINAL Not ready for Inspection FOLLOW PLANS: 1) I DO NOT SEE A SERVICE PANEL BOARD ON ELECTRICAL DIAGRAM. 2) INSTALL MAIN GROUNDING ELECTRODE CONDUCTOR TO NUETRAL TERMINATION IN C.T. CAN WITHOUT ANY SPLICER. 3) OPEN GUTTER. 4) NEED NUETRAL RUN TO EACH SERVICE DISCONNECT. 5) OTHER ITEMS PER PLAN TO BE FOLLOWED.