Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/23/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* | |
| 04/01/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 03/10/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* WHO IS LICENSED ELECTRICAL CONTRACTOR DOING THE WORK ON THIS DUPLEX RENTAL UNIT. 1.) WE ALSO HAVE GROUNDED RECEPTACLE ON AN UNGROUND SYSTEM. 2.) EXPOSE JUNCTION BOX FOR HALL FIXTURE WE ALSO HAVE LIVE PARTS WITH COMBUSTABLES. |
|
| 01/13/2003 | ELECTRIC - FINAL | Denied | 1.) FIND GUTTER COVER AND INSTALL IT 2.) THE TIE TO THE PANEL FOR THE GROUND TO BE A #6 ALSO 3.) NEED TO USE A DOUBLE POLE DOUBLE THROW 30A CB NOT TWO INDIVIDUAL ONES. 4.) THE GUTTER NEEDS TO BE RESECURED TO WOOD. 5.) THE KITCHEN RECEPTACLES BY THE SINK NEED TO BE GFCI PROTECTED. 6.) INSTALL THE NEW SMOKE DETECTOR IN THE BEDROOM AND AT LEAST 6" AWAY FROM ANY VERTICAL SURFACE. SUGGEST YOU OBTAIN A LICENSED ELECTRICAL CONTRACTOR FOR REPAIR. |