Permit: T03EL00040

Parcel: 12607029A


Addresses:

341 N LONGFELLOW AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/02/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARANCE INFRONT OF KITCHEN PANEL AS DISCUSSED.
2.) CHECK GAS BOND.
01/09/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
*REMOVE EXTENSION CORD WIRING AT KITCHEN CABINET (EAST OF SINK).
* ZIP CORD WIRING IS NOT ACCEPTABLE AT DISPOSAL
SWITCH & DISPOSAL
*OPEN SPLICE AT DISPOSAL NOT ALLOWED
*REMOVE EXTENSION CORD AT HALL BATH.
*GROUNDING TYPE RECEPTACLES NOT ALLOWED ON UNDERGROUND CIRCUITS UNLESS GFCI PROTECTE.
*OPEN LAMP FIXTURES NOT ALLOWED IN BEDROOM CLOSETS (REMOVE AND REPLACE.)
*SMOKE DETECTORS IN HALL MISSING BATTERY (INSTALL SMOKE DETECTORS AT ALL BEDROOMS)
*REMOVE PLUG STRIP AT EAST BATHROOM OR INSTALL PER NATIONAL ELEC. CODE.
* INSTALL ALL COVERS, PLATES ETC. WHEN PAINTING IS COMPLETED.* IMPROPER TAP AT MAIN SERVICE.
* PROPERLY WIRE THE WORK SHED OUT BACK
*OUTDOOR RECEPTACLES NEEDS TO BE WEATHER PROOF AND GFCI PROTECTED.