Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1/24/03 AT 9:15AM OK TO CLEAR PLEASE TIGHTEN NEUTRAL TERMANATION. | |
| 01/15/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) A PERMANENT METAL ADDRESS LABEL IS TO BE SCREWED OR RIVITED TO SERVICE. 2.) A GROUNDING ELECTRODE SYSTEM IS NEEDED FOR SERVICE UP GRADE. 3.) ALL BREAKERS ARE TO BE LABELED 4.) SUPPORT CONDUIT AS PER CODE AND TIGHTEN LOOSE FITTINGS 5.) AN APPROVED FITTING IS NEEDED AT LB A CHASE NIPPLE IS NOT APPROVED. 6.) PROTECT CABLES ENTERING PANEL. 7.) A BONDING DEVICE IS NEEDED ON SERVICE NIPPLE. 8.) SERVICE ENTRANCE CONDUCTORS TO BE SIZE PER AMPICITY OF MAN BREAKER. |