Permit: T03EL00034

Parcel: 133040430


Addresses:

9141 E HELEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1/24/03 AT 9:15AM OK TO CLEAR PLEASE TIGHTEN NEUTRAL TERMANATION.
01/15/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) A PERMANENT METAL ADDRESS LABEL IS TO BE SCREWED OR RIVITED TO SERVICE.
2.) A GROUNDING ELECTRODE SYSTEM IS NEEDED FOR SERVICE UP GRADE.
3.) ALL BREAKERS ARE TO BE LABELED
4.) SUPPORT CONDUIT AS PER CODE AND TIGHTEN LOOSE FITTINGS
5.) AN APPROVED FITTING IS NEEDED AT LB A CHASE NIPPLE IS NOT APPROVED.
6.) PROTECT CABLES ENTERING PANEL.
7.) A BONDING DEVICE IS NEEDED ON SERVICE NIPPLE.
8.) SERVICE ENTRANCE CONDUCTORS TO BE SIZE PER AMPICITY OF MAN BREAKER.