Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1/27/03 AT 9:15AM OK TO CLEAR. | |
| 01/13/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215* 1.) THE WIRING TO THE SUB PANEL (FROM THE 100 A.C.B. MUST BE DONE WITH WIRE. RATED 100A. THE EXCEPTION OF ART 310 15 DOES NOT APPLY TO THIS INSTALLATION. 2.) INSTALL A NEW GROUNDING SYSTEM FOR THE 200AMP SERVICE USING THE ITEMS ON THE DIAGRAM BELOW. RECALL WHEN COMPLETE THANKS. |