Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL00011
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. THANK YOU. | |
01/14/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 1/15/03 AT 9:15AM 1.) PLEASE LABEL OUTSIDE COVER OF PANEL 2.) PERMANENT METAL LABELS ARE NEEDED 3.) AN APPROVED CONNECTOR IS NEEDED FOR L.B. CHASE NIPPLE IS NOT APPROVED. 4.) PLEASE RECALL AFTER CROSS OVER. 5.) SUPPORT RISERS BELOW PANEL. OK TO CLEAR. |
|
01/13/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) NO COMPLIANCE WITH INSP WRITE UP ON 1-9-03. 2.) NO ANSWER AT DOOR 3325. |
|
01/09/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* *WHEN WAS THE UNDERGROUND INSPECTION APPROVED? *WHERE ARE THE APPROVED PLANS? *RESCHEDULE INSPECTION AND MAKE ARRANGEMENT THROUGH I.V.R. SYSTEM OR THROUGH RAY MAJUTA 791-5550 EXT 1136. TO MEET W/INSPECTOR ON SITE. |