Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03EL00002
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/15/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1/16/03 AT 9:15AM. | |
01/13/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*PLEASE CORRECT: 1.) THE RISER CONDUIT (ABOVE ROOF) REQUIRES A BRACE. SEE TEP SERVICE REQUIREMENTS MANUAL. 2.) THE GROUND WIRE AT THE FIRST ROD CLAMP NEEDS TO BE LOCATED IN THE POCKET AT FRONT OF CLAMP. 3.) LEAVE NOTE INDICATING WHERE COLD WATER AND GAS LINE GROUNDS ARE LOCATED. LEAVE HOUSE UNLOCKED IF GROUNDS ARE INSIDE. 4.) FOR FUTURE INSTALLATIONS PLEASE DO NOT USE CHASE NIPPLES TO CONNECT FITTINGS TO PANEL. USE THREADED NIPPLES AND LOCKNUTS. CHASE NIPPLE DO NOT PROVIDE ADEQUATE GROUNDING OF CONDUIT TO BOX. |