Case: T03DV00804

Parcel: 119211460


Addresses:

1605 W CIRCLE B DR


Inspection Status: Violation

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T03DV00804

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Violation

Date Description Inspector Results Comments
09/12/2003 INSP - INITIAL CODE ENFORCMENT Violation VIOLATIONS FOUND
VISITED SITE , MET WITH TENANT & WALKED PROPERTY. VIOLATIONS FOUND ARE AS FOLLOWS
(1) RECEPTACLES WERE TESTED THOUGH OUT STRUCTURE, REVERSED POLAIRITY IN KITCHEN OUTLETS, OPEN GROUNDS IN WEST,SOUTHWEST & SOUTH EAST BEDROOMS. RECEPTACLE COVER PLATES LACKING IN SOUTH EAST BEDROOM, FOR WASHING MACHINE & DYER RECEPTACLES. ELECTRICAL SERVICE HAS BEEN UP-GRADED, 2 PRONG RECEPTACLE WAS FOUND IN LAUNDRY ROOM. ADDITION OF 3 CIRCUTS, 1- FOR 220 OUTLET IN LAUNDRY ROOM. 1- FOR EXTERIOR LIGHTPOST IN BACK YARD WITH ELECTRICAL CONDUCTOR (ROMEX) NOT IN CONDUIT AND 1- 40 AMP BREAKER BOX WITH ELECTRICAL CONDUCTORS IN CONDUIT CONNECTED. THESE ITEMS ARE EVIDENCE OF W/O/P WILL DO RESEARCH & CHECKED FOR PERMITS.
(2) LACKING REQUIRED SMOKE DETECTOR.
(3) SOUTH EAST BEDROOM WINDOW CRANK NOT OPERATIONAL.
(4) DRYER LACKING EXHAUST VENT PIPE.
(5) NEW 30 GALLON HOTWATER HEATER HAS BEEN INSTALLED & IS LACKING DRAINPIPE FOR T.P.R. VALVE AND FLUE VENT JOINTS HAVE NOT BEEN SEALED. ALTERATION & ADDITION TO GAS PIPING FOR DRYER HAVE BEEN MADE. WILL DO RESEARCH & CHECK FOR PERMIT. PICTURES WERE TAKEN. WILL ISSUE N.O.V. WHEN RESEARCH IS COMPLETE.