Case: T03DV00608

Parcel: 13018074A


Addresses:

4250 E 29TH ST


Inspection Status: No Violation

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T03DV00608

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - No Violation

Date Description Inspector Results Comments
07/11/2003 INSP - INITIAL CODE ENFORCMENT No Violation 7/9/03, VISITED SITE, TALKED WITH RESIDENT WHO STATED THAT IT WAS HOT IN APT. AND THAT A/C UNIT WAS NOT WORKING, OUTSIDE TEMP. IS APPOX. 107, CHECKED A/C UNIT WITH INFRARED TEMPERATURE SENSEING DETECTOR, COLD AIR COMMING FROM A/C UNIT IS AT 48 DEGREES, INTERIOR TEMPERATURE OF APT. IS 75 DEGREES, BEDROOM TEMPERATURE IS 78 DEGREES, THERE IS A 5' WALL SEPERATING BEDROOM AND LIVING ROOM (STUDIO UNIT) WHICH BLOCKS ALOT OF THE AIR FLOW, EXPLAINED THAT RESIDENT NEEDED TO REMOVE ITEMS FROM THE TOP OF THE WALL AND READJUST THE DIRECTIONAL VENTS TO PUT MORE AIR CIRCULATION INTO BED ROOM, UNIT IS APPOX. 425 SQ. A/C UNIT IS A 1 TON A/C UNIT JUST ENOUGH OR MIN. REQUIREMENTS. MAINTENANCE HAD BEEN THERE THE PREVIOUS DAY AND DID SOME WORK AND CLEANED COILS PER RESIDENT. NO VIOLATION AT THIS TIME CLOSE CASE.