Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2003 | INSP - FOLLOW UP CODE ENFORCE | Compliance | ALL ITEM PER NOTICE REQUEST HAVE NOW BEEN ABATED, OK TO CLOSE AND TO RENT UNIT AGAIN. | |
| 08/25/2003 | INSP - FOLLOW UP CODE ENFORCE | Not ready for Inspection | UNABLE TO INSPECT THE UNIT OR BREAKER BOXES AGAIN, THE COMPLEX IS VERY SECURED, THE OWNER HAS NOT TRIED TO CALL ME FOR NEW INSPECTION AT THIS TIME, LETTER WILL BE SENT OUT TO RESPOND TO DNR. IF NO RESPONSE ----TICKET WILL BE WRITTEN. | |
| 07/14/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | INSPECTOR WAS CALLED TO UNIT 6 BY TUCSON FIER DEPT TO INVESTIGATE A POSSIBLE FIRE THREAT FROM THE ELECTRICAL WIRING IN THE UNIT. INSPECTOR DETERMINED THE FOLLOWING: 1) THE APARTMENT AND ALL ELECTRICAL APARATUS WITHIN ARE SERVED BY A SINGLE TWENTY AMP (20A) CIRCUIT BREAKER. 2) THE TOTAL CONNECTED ELECTRICAL LOAD EXCEEDS TWENTY AMPS. 3) THE PROBLEM MAY BE ELIMINATED BY EXTENDING ANOTHER TWENTY AMP CIRCUIT TO THE APARTMENT TO SERVE THE AC WINDOW UNIT ONLY. |