Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T03DV00509
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2004 | INSP - FOLLOW UP CODE ENFORCE | Approved | 03/17/2004 GIOIA ISSUED MOTION TO DISMISS COMPLAINT. GRANTED BY JUDGE LEAVITT. A REVISED COMPLAINT WILL BE ISSUED BY PROSECUTOR'S OFFICE. | |
| 02/03/2004 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | SITE VISIT TODAY-FOLLOW UP TO NOTICE AND ORDER, SOME ISSUES REMAIN, (IE) WEATHER SEALS ON UNIT E ARE REQUIRED ON BOTH DOORS, THIS UNIT WILL ALSO REQUIRE A PERMIT FOR THE HOTWATER HEATER, UNIT IS SAFE AT THIS TIME. ALSO THE UNIT REQUIRES A OVERFLOW COVER ON THE TUB AND THE SINK MOUNTED TO THE WALL, THE BASE IS VERY UNSTABLE. THE WASHROOM/SHED HAS NEW ELECT. CIRCUITS ADDED TO THE INSIDE IN THE FORM OF TWO 4-OUTLET BOXES, THERE IS ALSO GAS PIPES INSTALLED WITHOUT PROPER PERMITS IN SAME AREA. UNIT 320 B WILL REQUIRE REMOVAL OF HOTWATER HEATER OR PERMIT UNIT, THIS UNIT IS INSTALLED VERY IMPROPER AND UNSAFE. THE PROPERTY OWNER WAS GIVEN ANOTHER 30 DAYS TO FINISH ALL REPAIRS AND GET THE REQUIRED PERMITS FOR ALL HOTWATER HEATERS ON PROPERTY AND ELECT. PERMIT AND GAS PERMIT. THE OWNER WILL BE REQUIRED TO PULL A PERMIT ON 13 HOTWATER HEATERS. FOLLOW-UP INSPECTION DUE ON MARCH 2, 2004, THE PROPERTY OWNER WAS REQUESTED TO CONTACT DNR INSPECTORS WHEN AT DSD TO HELP WALK-THRU OF NEEDED PERMITS. |
|
| 12/31/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | AFTER ANOTHER EXTENSION WAS GRANTED TO THE OWNER. BELOW IS WHAT STILL IS NOT ABATED AND SHOULD BE CITED. 1) BOX #13 ON PAGE 5 OF ORIGINAL NOTICE, UNIT 324-D, UNSFAFE OR UNPERMITTED WORK. WATER HEATER NEEDS A PERMIT AND BROUGHT TO CODE. 2) BOX #16 ON PAGE 5 OF ORIGINAL NOTICE. UNIT 324-D. WEATHER PROTECTION - FRONT AND REAR DOORS LACK WEATHER STRIPPING. 3) BOX #17 ON PAGE 6 OF ORIGINAL NOTICE. UNIT 324-E - FRONT AND REAR DOORS LACK WEATHER STRIPPING. 4) BOX #21 ON PAGE 6 OF ORIGINAL NOTICE, UNIT 324-E, WATER HEATER NEEDS A PERMIT, NOT TO CODE. 5) BOX #42 ON PAGE 10 OF ORIGINAL NOTICE, UNSAFE FURNACE, FURNACE REQUIRES A PERMIT. 6) BOX #51 ON PAGE 11 OF ORIGINAL NOTICE, THE LAUNDRY ROOM WAS COMPLETELY REWIRED WITHOUT A PERMIT. PERMIT IS REQUIRED. 7) BOX #52 ON PAGE 11 OF ORIGINAL NOTICE, CONSTRUCTED AND ATTACHED AN AWNING/PORCH (APPROXIMATELY 6 FEET BY 20 FEET) WITH ELECTRICAL AND WATER HEATER WITHOUT A PERMIT. REQUIRES A PERMIT. |
|
| 11/20/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | CITATION THE FOLLOWING WILL BE SENT TO THE PROSECUTORS OFFICE. INSPECTED PROPERTY AGAIN ON 11/12/03 AND THE FOLLOWING VIOLATIONS WERE NOT ABATED. 1) BOX #3 OF NOV- UNIT 324-A, FURNACE WAS INSTALLED WITHOUT A PERMIT. 2) BOX #7 - UNIT 324-B - ELECTRICAL #1 - THERE ARE EXPPOSED ELECTRICAL WIRES LEADING TO AND HANGING DOWN AT THE CEILING FANS. #3) BOX #16 ON PAGE 5 OF NOV - UNIT 324-D - WEATHER PROTECTION- #1- THE FRONT AND REAR DOORS ARE LACKING PROPER WEATHER STRIPPING. #4) BOX 13 ON PAGE 5, UNIT 324-D, #1- UNSAFE OR UNPERMITTED WORK- WATER HEATER NEEDS A PERMIT. #5) BOX #14 ON PAGE 5 OF NOV, UNIT 324-D - INTERIOR FEATURES- #2 AND #3 - THE ARE TILES MISSING AND HOLES IN THE WALLS. THE CABINETS ARE BROKEN. #6) BOX 15 ON PAGE 5,UNIT 324-D, INTERIOR SANITATION - UNIT HAS PRESENCE OF LIVE ROACHES AND NEEDS EXTERMINATED. #7) BOX #17 ON PAGE 6 OF NOV. UNIT 324-E, WEATHER PROTECTION- THE FRONT AND REAR DOORS NEED PROPERLY WEATHER STRIPPED. #8) BOX #21 ON PAGE 6 OF NOV, UNIT 324-E- UNSAFE AND UNPERMITTED WORK. THE WATER HEATER NEEDS TO BE PERMITTED THROUGH DSD. #9) BOX #22 OF NOV ON PAGE 6 OF NOV -UNIT 324-F, WATER HEATER NOT TO CODE AND NEEDS A PERMIT. #10) BOX #42 ON PAGE 10 OF NOV., UNIT 320-A - HEATING - THE FURNACE IS INOPERABLE. ( A SAFE AND OPERABLE FURNACE IS REQUIRED AND MUST BE MAINTAINED IN A SAFE CONDITION. #11) BOX #44 ON PAGE 10 OF NOV. THE LAUNDRY ROOM THAT ALL TENANTS USE IS USING THE SAME WATER SUPPLY THAT IS HOOKED TO 320-A. ( THE LAUNDRY ROOM NEEDS TO HAVE ITS OWN WATER SUPPLY SO THAT THE UNIT WILL HAVE ADEQUATE POTABLE WATER SUPPLY. #12) BOX #51 ON PAGE 11 OF NOV. LAUNDRY ROOM - WORK WITHOUT PERMITS - THE LAUNDRY ROOM HAS BEEN REWIRED WITHOUT OBTAING A PERMIT. #13) BOX #52 ON PAGE 11 OF NOV., PORCH/AWNING ( APPROXIMATELY 6 X 20 FEET) ATTACHED TO 320 A AND B WITH ELECTRICAL AND A WATER HEATER INSTALLED. ALL THIS WORK NEEDS A PERMIT. #14) BOX #53 ON PAGE 11 OF NOV., ADDRESSING OF COMPLEX AND UNITS IS NOT PROPER ACCORDING TO TFC AND PIMA COUNTY ADDRESS CODE. #15) BOX #54 ON PAGE 11 OF NOV., NUISANCE, SANITATION, FIRE HAZARD - THERE IS AN ACCUMULATION OF JUNK, GARBAGE, AND DEBRIS, WEEDS THROUGHOUT THE PROPERTY THYAT NEEDS TO BE REMOVED. #16) BOX #56 ON PAGE 12 OF NOV., JMV,S - THERE ARE NUMEROUS JUNK MOTOR VEHICLES ON THE PROPERTY THAT ARE IN VIOLATION OF THE CITY CODE. |
|
| 10/03/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | THE OWNER IS MAKING PROGRESS ON THE PROPERTY. NO PERMITS HAVE BEEN OBTAINED YET FOR 2 WATER HEATERS OR THE NEW ELECTRICAL IN THE LAUNDRY ROOM. AN EXTENSION WAS GRANTED FOR THE OWNER TO FINISH UP ALL VIOLATIONS AND OBTAIN PERMITS. WILL REINSPECT ON 11/03/03. ELECTRICAL HAS BEEN DISCONNECTED/ SHUT OFF AT UNIT 320-B AND IS BEING USED FOR STORAGE OF MATERIALS. | |
| 10/02/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | ANOTHER EXTENSION WAS GRANTED TO THE OWNER. THE REINSPECTION WILL BE CONDUCTED TODAY. | |
| 09/17/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | NOTICE AND ORDER WENT OUT ON 8/6/03. REINSPECTION IS SCHEDULED FOR 9/30/03. | |
| 08/01/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | INSPECTED TODAY TO SEE IF THE ELECTRICAL HAZARDS HAD BEEN ABATED. THE MAIN SUPPLY THAT WAS HANGING DOWN ON THE BACK SIDE OF THE 6-PLEX HAS BEEN RESECURED. THE LAUNDRY ROOM ELECTRICAL WAS ALSO REPAIRED, HOWEVER, NO PERMIT WAS OBTAINED FOR THE 2 NEW 4-PLEX ELECTRICAL RECEPTACLES INSTALLED. THERE IS NO PERMIT FOR THE LAUNDRY ROOM FOUND.THIS WILL BE INCLUDED IN THE SABER NOTICE. | |
| 07/29/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | ALL UNITS HAVE BEEN INSPECTED AT THIS TIME AND THE RESEARCH IS COMPLETE WITH THE RECORDS THAT ARE AVAILABLE. I AM IN THE PROCESS OF PUTTING THE NOTICE TOGETHER. IT SHOULD GO OUT THIS WEEK. | |
| 07/02/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | WENT BY UNIT F OR 6 TO REINSPECT. NO ONE WAS HOME. MOST OF THE REPAIRS ARE DONE AS OF LAST INSPECTION. THIS UNIT WILL BE REINSPECTED AGAIN WHEN ALL UNITS ARE INSPECTED FOR COMPLIANCE UNDER THE SABER NOTICE. | |
| 06/30/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | CECI AND I INSPECTED UNIT B ON 6/27/03. MANY MINIMUM HOUSING VIOLATINS WERE FOUND. THIS WAS THE LAST UNIT TO BE INSPECTED. SOME RESEARCH STILL NEEDS TO BE DONE AND NOTES FROM ALL THE INSPECTORS TURNED INTO ME BEFORE THE NOTICE CAN BE STARTED. | |
| 06/24/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | THE ELECTRICAL THAT WAS UNSECURED AND FALLING HAS BEEN REPAIRED. THE OWNER WAS GIVEN A 5 DAY NOTICE TO REPAIR. IT HAS BEEN REPAIRED. | |
| 06/24/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | UNITS WERE PREVIOUSLY POSTED WITH INTENT TO INSPECT. TODAY ALL UNITS EXCEPT UNIT #B WERE INSPECTED. THE OWNERS HOUSE WAS NOT INSPECTED EITHER BECAUSE THERE WAS NO REASON TO JUSTIFY ENTERING HER HOUSE. THE OTHER 11 UNITS WERE INSPECTED. | |
| 06/19/2003 | INSP - FOLLOW UP CODE ENFORCE | Compliance | 5 NOTICE FOR THE REAR CONDUIT AND ELECT. FEEDERS ARE ABATED PER REQUEST. UNITS A-F. OTHERS ITEMS REMAIN PENDING SABER NOTICE TO OWNER. | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | COMMON AREA;;;;;;;;;;SITE VISIT I DID NOT FIND ANY CORDS RUNNING ACROSS THE DRIVE, I DID FIND A FEW OTHER ISSUES THAT WILL NEED TO BE ABATED. AS FOLLOWS: SIDEWALK HAS BROKEN CONCRETE VERY UNSAFE. PROPERTY FENCE FALLING THRU-OUT , PRIVATE YARDS ALSO. FACE BOARD AT ROOF LINE IS ROTTON AND 50% PAINT PEELING. SPLICED ELECT. PORCH LIGHT. MISSING WEATHER SEALS ON ALL WINDOWS AND DOORS. DROP CORDS. HAD OWNER AND MAINT REMOVE POWER CORDSTO THE WASHROOM WHILE AT SITE. JUNK AND DEBRIES THRU-OUT LOT(IE) CARS,TRASH,CAR BATTERIES. MAIN ELECT. SUPPLY CONDUIT IS LACKING PROPER SUPPORT ON THE REAR OF BUILDING.;;SPOKE TO C-6 ABOUT CASE AND WOULD MAKE A SABER ? C-6 WANTS TO DO A INSPECTION OF PROPERTY...NOV OUT. |
|
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | OWNER LIVES AT SITE IN MAIN HOUSE, # 294-2454, MARY COLYER, OWNER STATED THAT C-6 AND C-11 WAS AT SITE A WHILE BACK ON A DIFFERENT UNIT. | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | WILL BE SABER CASE PER C-6 | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | UNIT G; THERMOSTAT HANGING FROM WALL. KITCHEN SINK LEAKING WATER AT DRAIN. NO CONDUIT ON C-FAN ELECT.WIRES. NO WORKING SMOKE DECT. BATH TILE BROKEN IN SHOWER. NO WEATHER SEALS AROUND BOTH DOORS. FRONT DOOR LOCKS BROKEN. FRONT DOOR BOTTOM HALF ROTTON.. TUB OVER FLOW DRAIN COVER BROKEN. |
|
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | UNIT D; NO WORKING SMOKE DECT. BATHROOM WALL PLASTER WATER DAMAGED AND LOOSE NEAR TUB. MISSING COVER GUARD IN BREAKER BOX. NO WEATHER SEALS ON BOTH DOORS. REAR DOOR WILL NO LOCK,MISSING. FENCE IN REAR YARD ROTTEN AND UNSTABLE. MAIN ELECT.CONDUIT SUPPORT IS LOOSE MOUNTED ON REAR OF UNIT. |
|
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | HOLD NOV ;PENDING SABER.SEE C-6 | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | DID SITE INSPECTION AGAIN TODAY PER C-6 REQUEST, GLEN FROM T.F.D ALSO AT SITE, WE DID A WALK AROUND THE LOT AND I INSPECTED ANOTHER UNIT; | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | UNIT # C; THE FOLLOWING ITEM WILL NEED ABATED; SLICED CORD TO C-FAN.BROKEN WINDOW IN BEDROOM. NO SMOKE DECT IN BEDROOMS. COVER PLATE MISSING ONE AT BREAKER BOX. SINK BROKEN AWAY FROM WALL. ROOF LEAKING. NO WEATHER SEALS AT BOTH DOORS. PLASTER LOOSE ABOVE TUB. |
|
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | NOTICE WROTE AT SITE. LARGE FEEDER CONDUIT TO THE REAR OF UNIT A-F IS LOOSE AND UNSTABLE, NOV WROTE AT SITE PER C-6 REQUEST. 5 DAYS GIVEN TO INSTALL NEW CLAMPS TO SECURE. |
|
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | UNIT E; IS UNDER C-11 AT THIS TIME THERE IS A NOV OUT. | |
| 06/12/2003 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | FIRE, DNR CONDUCTED AN INSPECTION TODAY OF THE EXTERIOR UNITS AND THE LAUNDRY ROOM. ZONING ALREADY HAS A CASE OUT THERE OR OPENING ONE SOON. THIS WAS REFERRED BY ZONING. SOLID WASTE ALSO HAS MANY ISSUES. 2 NOTICES WERE HAND WROTE TODAY. ONE FOR DANGEROUS ELECTRIC ( ONE DAY NOTICE) IN THE LAUNDRY ROOM WHICH THE OWNER HAD THE MAINTENANCE MAN DISCONNECT WHILE WE WERE THERE. THE OTHER WAS A 5 DAY NOTICE FOR THEM TO SECURE MAIN POWER LINES AT THE REAR OF THE BUILDING. THERE ARE 13 UNITS ON SITE, SOME OF WHICH ARE ILLEGAL ACCORDING TO RECORDS. THIS SHOULD BE A SABER CASE AS RECOMMENDED. |